[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

RE: Y2K problems at a Nuke Plant?



While this is not an optimal way to test for Y2K compliance, that is testing
the backup and primary systems instead of just the backup, it is important
to note that these systems are data monitoring systems and not active
control systems.

... mine and mine alone ...

Ron LaVera
lavera.r@nypa.gov

-----Original Message-----
From: Julie_F_Shafer@fpl.com [mailto:Julie_F_Shafer@fpl.com]
Sent: Wednesday, March 03, 1999 12:06 PM
To: Multiple recipients of list
Subject: Re: Y2K problems at a Nuke Plant?



I found the following article:

at:
http://www.euy2k.com/newsroom.htm

Pa. Nuclear Plant Loses Monitoring System Computers During Y2k Testing

Rockville, Md. (February 26) - PECO Energy's Peach Bottom Unit 2 nuclear
facility near York, Pa. recently experienced a 7 hour lockup of the plant's
primary and backup plant monitoring system computers during Y2k testing. The
NRC
weekly summary of 2/12/1999 reports that operators lost the plant's Safety
Parameter Display System (SPDS), Emergency Response Data System (ERDS), and
3D
Monicore thermal limit monitoring system during the event.

Engineers had taken the backup PMS computer off-line and had advanced the
PMS
clock to a year 2000 Date. This led to a lockup of the backup PMS, and the
system transferred to the primary, on-line PMS computer. The engineers did
not
recognize that the system had transferred and, believing that the original
command was not accepted, again advanced the system clock, causing the
primary
PMS to lock up also. Several initial attempts to restore the PMS computers
were
unsuccessful, and operators determined that this constituted a major loss of
emergency assessment capability. The PMS computers are not Y2K compliant,
but
the engineers believed that this would not impact the testing. Operators did
not
expect the testing would affect the on-line PMS computer. PECO Energy plans
to
perform a full root cause analysis of this event.

Julie Shafer


************************************************************************
The RADSAFE Frequently Asked Questions list, archives and subscription
information can be accessed at http://www.ehs.uiuc.edu/~rad/radsafe.html
************************************************************************
The RADSAFE Frequently Asked Questions list, archives and subscription
information can be accessed at http://www.ehs.uiuc.edu/~rad/radsafe.html